Vitreous LabsEnergy transparency
Great Britain · the operating fleet

Port of Tyne Energy Storage

35 MW, about 24 MWh (0.7 hours, measured from its behaviour) in North East England. Everything on this page is read from published data for the 364 days to 16 October 2026, or is labelled as an estimate.

What it is

Registered power35 MW balancing mechanism registration
Storage duration0.7 hours measured from twenty one days of behaviour
Charging zoneNorth East England
Connection sitePort of Tyne
Balancing mechanism unitE_POTES-1

Who owns it and who trades it

Traded byArenko Cleantech Limitedruns several sitesconfirmed, Elexon's register
Owned bySOUTH SHIELDS ENERGY STORAGE LTD
Owner established fromcapacity market registered holder
UltimatelyGresham House Energy Storage Fund confirmed source

How we know. The fund announced buying Port of Tyne and Nevendon on 1 February 2021.

Market registers name the party that sells into the market, which for a battery is usually an optimiser under contract rather than the owner. Elexon's balancing mechanism unit register names the seller here and the name is checked against it on every build. How we tell them apart

What it is built from

Engineering and constructionRES developed, built and initially operated it
Entered operation2018 (commissioned early 2018 for a four year Enhanced Frequency Response contract)

From published documents, not from any register: supplier and contractor project pages, owner announcements and the trade press. Confidence: confirmed. Checked 2026-08-31. source 1 · source 2. Fields not shown are not published anywhere we have found, and we do not guess them.

What it earned

Line364 days to 16 October 2026
Balancing mechanism£102k
Response and reserve auctions auction implied£1.1m
Capacity market£1.0m
Three lines together£2.2m

Balancing is offer revenue and does not net off the cost of the power. The response and reserve figure is the value implied by the published auction results, award quantity times clearing price times the length of the delivery window, and not a settled payment. Capacity market income is the cleared price raised for inflation where the auction set a base period, split by month on EMRS's weights. Method

Outside the balancing mechanism, derived from the meter

Elexon publishes what this unit's meter recorded every half hour. Take away the balancing volumes NESO accepted and what is left is the position the unit ran outside the balancing mechanism: its wholesale trading, its frequency response delivery, and its losses, together. This unit held a frequency response contract in 15,678 of those half hours. The energy the contract asked of it, contracted megawatts times NESO's published delivery curve at the measured grid frequency, is taken out of the position and valued at the imbalance price, because it sits outside the unit's declared position and that is the price Elexon settles it at. What remains is the traded position, valued at the market index. In 17 half hours a contract was held but the grid frequency is not yet held, so those are left in the traded position. The volumes are measured. The prices are public benchmarks, not this unit's trades. The product is derived, and is shown apart from the three measured lines above. 359 days to 11 October 2026, 45 of them still provisional in Elexon's settlement runs. Method and caveats

LineMWh or £
Metered export, what crossed the meter out4,597 MWh
Metered import, what crossed the meter in5,955 MWh
Equivalent full cycles, everything sent out over one full charge188 over 359 days, 191 a year at that rate
Apparent meter to meter efficiency77%, plausible: losses plus a standing load that is material against a modest throughput
Balancing offers accepted2,013 MWh
Balancing bids accepted1,924 MWh
Position outside balancing, export4,342 MWh
Position outside balancing, import5,789 MWh
Of which expected response delivery, net−172 MWh 1,195 out, 1,367 in
Traded position, net−1,275 MWh 4,120 out, 5,395 in
Traded position at the market index, sold£465k
Traded position at the market index, bought£477k
Traded position, net, at the index−£12k
Response delivery, net, at the imbalance price−£30k −£23k at the index
Balancing and outside balancing together£61k £1.76/kW/yr

When it moved, against when power was dear

Across every half hour this unit was metered the market index averaged £97.34. What it sent out was worth £112.91 a megawatt hour at that same index, 1.16 times the average. What it took in was worth £88.45, 0.91 times. Selling above one and buying below one is a unit positioned into the dear half hours and out of the cheap ones. It measures the half hours it chose, not the price anyone paid it, which is not published.

What it paid to buy energy back

When NESO accepts a bid, this unit delivers less than it had already sold, or takes more in. It pays for the energy it no longer delivers, and that payment is most of what makes the balancing figure above negative. Whether that is a cost or a margin depends on the price it paid. Across 1,924 MWh of accepted bids it paid an average of £68.38 a megawatt hour. The market index averaged £99.71 across those same half hours, so it bought back at £31.33 a megawatt hour below the going price.

Price it paidVolumeAverageCash
below zero109 MWh−£20.40£2k received
£0 to £2580 MWh£12.82£1k
£25 to £50152 MWh£37.78£6k
£50 to £75617 MWh£64.99£40k
£75 to £100828 MWh£86.73£72k
above £100138 MWh£109.11£15k

On 109 MWh the price was below zero: NESO paid this unit an average of £20.40 a megawatt hour to take energy, £2k in all. That is a constrained network with more generation on it than it can move.

The other direction, offers, is much smaller here: 2,013 MWh where NESO asked for more, paid at an average of £116.42 against an index of £89.74.

Physical checks passed: the meter never exceeded the registered power by more than fifteen per cent, and the year's exports against imports are what a battery does.

Where it stands

Balancing incomewhole fleet, £/kW/yr16th percentile100 units
Balancing incomeEngland and Wales peer group10th percentile72 units
Balancing income0.7 hour duration cohort19th percentile22 units
All three measured lineswhole fleet, £/kW/yr73rd percentile230 units
Energy sent outhours at full power31st percentile98 units
Energy taken inhours at full power9th percentile98 units

Percentiles, so 90 means better than nine in ten of the cohort named beside it, on that measure alone, over the same 364 days. Rates are pounds per kilowatt per year, annualised over the days the unit has been on the system, the same figures the performance league ranks on. A high position in the taken-in table is not a fault: a constraint asset is paid to charge, and charging is its job.

The nearest comparables

The five nearest in size in England and Wales, and this battery among them, ranked by what each was paid for every kilowatt it holds over the 364 days to the same date. They run for about the same length of time. Same market, same rules, same weather.

BatteryMWHoursMeasured, per kW
Maldon361h£107.5/kW/yr
Port of Tyne Energy Storagethis battery350.7h£63.0/kW/yr
Loudwater331h£62.7/kW/yr
Fareham Reserve 2361h£44.5/kW/yr
Potmans Lane351h£27.8/kW/yr
Conrad (FLITWICK)361h£16.1/kW/yr

See it on the map

Open the operating map here

Every figure on this page traces to a published file. If something here is wrong about your asset, the methods section says how to tell us.